ClimaSys forced vent. IP54, 300m3/h, 115V, with outlet grille and filter G2 - NSYCVF300M115PF
DESCRIPTION
| Lead time: | Usually Ships within 4 Weeks |
|---|
| Range: | ClimaSys |
|---|---|
| Product name: | ClimaSys CV |
| Product or component type: | Fan |
| Type of ventilation filter: | Standard |
| Air flow: | Free flow rate with standard filter: 300 m3/h at 50 HzFree flow rate with standard filter: 350 m3/h at 60 Hz |
| [Us] rated supply voltage: | 75...126 V |
| Input voltage: | 115 V 50/60 Hz |
| Power range: | 36 W 50 Hz36 W 60 Hz |
|---|---|
| [In] rated current: | 0.35 A 50 Hz0.32 A 60 Hz |
| Noise level: | 55...56 dB |
| Bearing type: | Ball |
| Height: | 268 mm external: |
| Width: | 248 mm external: |
| Depth: | 116 mm external: |
| Cut-out dimensions: | 223 x 223 mm |
| Product weight: | 1.3 kg |
| Material: | Outlet grille: injected thermoplastic (ASA PC) |
| Colour: | Outlet grille: grey (RAL 7035) |
| Ambient air temperature for operation: | -10...70 °C |
| Ambient air temperature for storage: | -40...70 °C |
| Maximum pressure: | 158 Pa flow rate 0 m³/h |
| Connections - terminals: | Faston connector |
| IP degree of protection: | IP54 |
| Device composition: | 1 axial motor2 protective grille: on the front and rear surfaces1 filter: front of axial motor1 outlet grille: front1 cut-out template1 power cord |
| Condition of use: | Flow rates depends on the work point, see ProClima softwareSurrounding environment must be relatively cleanOutside temperature must be 5 °C lower than inside temperatureFilter must be cleaned and replaced regularlyOverfrequent filter replacement should be avoided |
| Sustainable offer status: | Green Premium productREACh Regulation |
| Code EAN: | 3606480151293 |
|---|