ClimaSys forced vent. IP54, 85m3/h, 48V DC, with outlet grille and filter G2 - NSYCVF85M48DPF
DESCRIPTION
| Range: | ClimaSys |
|---|---|
| Product name: | ClimaSys CV |
| Product or component type: | Fan |
| Type of ventilation filter: | Standard |
| Air flow: | Free flow rate with standard filter: 79 m3/h |
| [Us] rated supply voltage: | 25...55.2 V |
| Input voltage: | 48 V DC |
| Power range: | 8 W |
|---|---|
| [In] rated current: | 0.173 A |
| Noise level: | 46...49 dB |
| Bearing type: | Ball |
| Height: | 170 mm external: |
| Width: | 150 mm external: |
| Depth: | 62 mm external: |
| Cut-out dimensions: | 125 x 125 mm |
| Product weight: | 0.48 kg |
| Material: | Outlet grille: injected thermoplastic (ASA PC) |
| Colour: | Outlet grille: grey (RAL 7032) |
| Ambient air temperature for operation: | -10...70 °C |
| Ambient air temperature for storage: | -40...70 °C |
| Maximum pressure: | 50 Pa flow rate 0 m³/h |
| Connections - terminals: | Cable |
| IP degree of protection: | IP54 |
| Device composition: | 1 axial motor2 protective grille: on the front and rear surfaces1 filter: front of axial motor1 outlet grille: front1 cut-out template1 power cord |
| Condition of use: | Surrounding environment must be relatively cleanFilter must be cleaned and replaced regularlyOutside temperature must be 5 °C lower than inside temperatureOverfrequent filter replacement should be avoidedFlow rates depends on the work point, see ProClima software |
| Sustainable offer status: | Green Premium product |
|---|---|
| REACh Regulation: | Free of Substances of Very High Concern above the threshold |
| REACh free of SVHC: | Yes |
| EU RoHS Directive: | Compliant |
| Mercury free: | Yes |
| RoHS exemption information: | Yes |
| China RoHS Regulation: | Product out of China RoHS scope. Substance declaration for your information |
| Environmental Disclosure: | ENVPEP110717EN_V0 |
| Circularity Profile: | ENVEOLI1107017_V0 |
| Code EAN: | 3606480151231 |
|---|