Linergy LGY - Profil pour JdB vertical - 1250A - L= 1670mm - LVS04505
DESCRIPTION
| Range: | Linergy |
|---|---|
| Range of product: | Linergy |
| Product or component type: | Profile busbar |
| Product name: | Linergy LGY |
| Range compatibility: | PrismaSeT P enclosure |
| Busbar description: | Linergy |
| Quantity per set: | Set of 1 |
| Installation direction: | Vertical, operating position: rearVertical, operating position: lateral |
|---|---|
| Enclosure/cubicle description: | Cubicle - width 650 mmCubicle - width 650 + 150 mm |
| [Ui] rated insulation voltage: | 1000 V |
| [Uimp] rated impulse withstand voltage: | 12 kV (degree of pollution: 3) |
| [Ie] rated operational current: | 1250 A |
| [Icw] rated short-time withstand current: | 25 kA (1 s) for 3 supports (rear position)30 kA (1 s) for 4 supports (rear position)40 kA (1 s) for 3 supports (lateral position)40 kA (1 s) for 5 supports (rear position)50 kA (1 s) for 4 supports (lateral position)60 kA (1 s) for 5 supports (lateral position)50 kA (1 s) for 7 supports (rear position) |
| Permissible current: | 1290 A at 35 °C: 1170 A at 35 °C: > IP31 |
| Busbar cross section: | 32.5 x 42.5 mm |
| Length: | 1670 mm |
| Net weight: | 3.38 kg |
| Colour: | Natural |
| Type of busbar connection: | Single t-slot |
| Connection pitch: | Free connection position |
| Compatibility code: | Linergy_busbar |
| Standards: | IEC 61439-2IEC 61439-1 |
|---|---|
| Product certifications: | ASTA |
| Sustainable offer status: | Green Premium productREACh Regulation |
| Code EAN: | 3606481870346 |
|---|