Miniature circuit-breaker, Acti9 iC60N, 2P, 10 A, C curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2) - A9F77210
DESCRIPTION
-
- Main
- device application : Distribution
- range : Acti 9
- range of product : IC60
- product name : Acti 9 iC60
- product or component type : Miniature circuit-breaker
- device short name : IC60N
- poles description : 2P
- number of protected poles : 2
- [In] rated current : 10 A
- network type : DC AC
- trip unit technology : Thermal-magnetic
- curve code : C
- breaking capacity code : N
- breaking capacity: 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
- Main
- 36 kA Icu at 12... 60 V AC 50/60 Hz conforming to EN/IEC 60947-2
- 10 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
- 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
- 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
- 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
- 36 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
-
- use category : Category A conforming to EN 60947-2
- Category A conforming to IEC 60947-2
- suitability for isolation : Yes conforming to EN 60898-1
- Yes conforming to EN 60947-2
- Yes conforming to IEC 60898-1
- Yes conforming to IEC 60947-2
- standards : EN 60947-2
-
- EN 60898-1
- IEC 60898-1
- IEC 60947-2
-
-
- quality labels : NF
-
The iC60 Acti9 modular circuit breaker is the new benchmark in low-voltage terminal distribution for circuit protection. Thanks to its exclusive features, it offers absolute safety and improved service continuity: iClass 2 insulation, VISI-TRIP: rapid detection of faults, harsh environments: ‘Si’ type device fully immune to electrical disturbances.
-
- Rated current: 1 to 63 A and breaking capacity up to 100 kA
- Operating voltage: up to 440 Vac, insulation voltage: 500V, pollution degree: level 3.
- Auxiliaries: status and trip indicator, voltage emission trip, undervoltage trip, overvoltage trip.
- Environmental characteristics
-
- Period : 18 months
- Environmental status : Green Premium product
- RoHS (code date: YearWeek) : Compliant - since 1001 - Schneider Electric declaration of conformity
- REACh : Reference not containing SVHC above the threshold
- Product environmental profile : Available
- End-of-life instructions for the product : No specific recycling operations
- Device function : Distribution
- Range : Acti 9
- Product function : Miniature circuit breaker
- Product name : IC60
- Abbreviated device name : IC60N
- Pole description : 2P
- Number of protected poles : 2
- Rated operating current : 10 A
- Network type : AC DC
- Trigger technology : Thermal-magnetic
- Trigger curve : C
- Breaking capacity : 36 kA Icu in accordance with EN 60947-2 - 12...133 V AC 50/60 Hz
- 36 kA Icu in accordance with IEC 60947-2 - 12...133 V AC 50/60 Hz
- 6 kA Icu in accordance with IEC 60947-2 - 440 V AC 50/60 Hz
- 6 kA Icu in accordance with EN 60947-2 - 440 V AC 50/60 Hz
- 20 kA Icu in accordance with IEC 60947-2 - 220... 240 V AC 50/60 Hz
- 20 kA Icu in accordance with EN 60947-2 - 220...240 V AC 50/60 Hz
- 10 kA Icu in accordance with IEC 60947-2 - 380...415 V AC 50/60 Hz
- 10 kA Icu in accordance with EN 60947-2 - 380...415 V AC 50/60 Hz
- 10 kA Icu in accordance with IEC 60947-2 - 72...125 V DC
- 10 kA Icu in accordance with EN 60947-2 - 72... 125 V DC
- 6000 A Icn in accordance with IEC 60898-1 - 400 V AC 50/60 Hz
- 6000 A Icn in accordance with EN 60898-1 - 400 V AC 50/60 Hz
- Category of use : A in accordance with IEC 60947-2
- A in accordance with EN 60947-2
- Switching capability : Yes in accordance with IEC 60947-2
- Yes in accordance with IEC 60898-1
- Yes in accordance with EN 60947-2
- Yes in accordance with EN 60898-1
- Standards : EN 60898-1
- EN 60947-2
- IEC 60898-1
- IEC 60947-2
- Quality labels : NF
- Mains frequency : 50/60 Hz
- Magnetic trip limit : 8 x In +/- 20%
- [Ics] rated short-circuit breaking capacity : 10 kA 100% x Icu in accordance with EN 60947-2 - 72...125 V DC
- 10 kA 100% x Icu in accordance with IEC 60947-2 - 72...125 V DC
- 6000 A 100% x Icu in accordance with IEC 60898-1 - 400 V AC 50/60 Hz
- 6000 A 100% x Icu in accordance with EN 60898-1 - 400 V AC 50/60 Hz
- 27 kA 0.75 x Icu in accordance with EN 60947-2 - 12...133 V AC 50/60 Hz
- 27 kA 0.75 x Icu in accordance with IEC 60947-2 - 12...133 V AC 50/60 Hz
- 4.5 kA 0.75 x Icu in accordance with IEC 60947-2 - 440 V AC 50/60 Hz
- 7.5 kA 0.75 x Icu in accordance with IEC 60947-2 - 380...415 V AC 50/60 Hz
- 15 kA 0.75 x Icu in accordance with IEC 60947-2 - 220...240 V AC 50/60 Hz
- 4.5 kA 0.75 x Icu in accordance with EN 60947-2 - 440 V AC 50/60 Hz
- 7.5 kA 0.75 x Icu in accordance with EN 60947-2 - 380...415 V AC 50/60 Hz
- 15 kA 0.75 x Icu in accordance with EN 60947-2 - 220...240 V AC 50/60 Hz
- Limitation class : 3 in accordance with IEC 60898-1
- 3 in accordance with EN 60898-1
- [Ui] rated insulation voltage : 500 V AC 50/60 Hz in accordance with IEC 60947-2
- 500 V AC 50/60 Hz in accordance with EN 60947-2
- [Uimp] rated impulse withstand voltage : 6 kV in accordance with IEC 60947-2
- 6 kV in accordance with EN 60947-2
- Fully visible break : Yes
- Type of control : By cam
- Local signalling : Trip indicator
- Installation mode : Fixed
- Mounting bracket : DIN rail
- Compatibility of busbar comb distribution block : Yes, top or bottom
- 9 mm pitch : 4
- Height : 85 mm
- Width : 36 mm
- Depth : 78.5 mm
- Weight : 0.25 kg
- Colour : White
- Mechanical life : 20,000 cycles
- Electrical life : 10,000 cycles
- Connection method : Single terminal, top or bottom flexible wire(s) 1...16 mm² max
- Single terminal, top or bottom rigid wire(s) 1...25 mm² max
- Wire stripping length : 14 mm top or bottom
- Tightening torque : 2 N.m top or bottom
- Earth leakage protection : Separate bloc
-
| Code EAN: | 3606480094125 |
|---|---|
| Rappels: | This Schneider A9F77210 circuit breaker is a miniature circuit breaker from the Acti9 range, iC60N 2P 10A C-curve circuit breaker - A9F77210. It protects 2P and has a thermal-magnetic trip type. It has a consumption of 10 A and a C curve trip designed for the following applications: general applications. The breaking capacity is 20 kA at 220...240 V and 10 kA at 380...415 V. We confirm that this circuit breaker occupies two modules in width and can be housed in a cabinet or box. It can be connected with rigid wires of 25 mm² max. or flexible wires of 16 mm² max. |