modular single phase power meter iEM2135 - 230V - 63A with comm M-Bus - MID - A9MEM2135
DESCRIPTION
| Range: | Acti9 |
|---|---|
| Product name: | Acti9 iEM2100 |
| Device short name: | iEM2135 |
| Product or component type: | Energy meter |
| Market segment: | Buildings small building cost management: billing: panelboardBuildings medium building cost management: billing: panelboardBuildings large building cost management: billing: panelboardBuildings multi-site cost management: billing: panelboardData center cost management: billing: panelboardHealthcare cost management: billing: panelboardIndustry cost management: billing: panelboardBuildings small building cost management: cost allocation: panelboardBuildings medium building cost management: cost allocation: panelboardBuildings large building cost management: cost allocation: panelboardBuildings multi-site cost management: cost allocation: panelboardData center cost management: cost allocation: panelboardHealthcare cost management: cost allocation: panelboardIndustry cost management: cost allocation: panelboard |
| Poles description: | 1P + N |
|---|---|
| Type of measurement: | Active and reactive energyActive and reactive powerCurrentVoltagePower factorFrequency |
| Metering type: | Active, reactive, apparent energy (signed, four quadrant) |
| Device application: | Sub billingPartial meterMulti-tariff |
| Accuracy class: | Class 1 active energy conforming to IEC 62053-21Class B active energy conforming to EN 50470-3Class 2 reactive energy conforming to IEC 62053-23 |
| Analogue input type: | Direct input |
| Max current: | 63 A |
| [Ib] basic current: | 5 A |
| [In] rated current: | 63 A |
| Rated voltage: | 230 V +/- 20 % |
| Network frequency: | 50 Hz60 Hz |
| Frequency measurement range: | 45...65 Hz |
| Technology type: | Electronic |
| Display type: | LCD display |
| Sampling rate: | 32 samples/cycle |
| Measurement current: | 0.25...63 A |
| Display digits: | 8 |
| Maximum value measured: | 999999.99 kWh |
| Information displayed: | Tariff (2) |
| Communication port protocol: | M-bus at 300, 600, 1200, 2400, 4800 and 9600 bauds - 2 wires, insulation 3750 V |
| Communication port support: | Screw terminals: M-Bus |
| Local signalling: | Red LED: accuracy checking 1...1000 p/kWh |
| Number of inputs: | 1 digital |
| [Us] rated supply voltage: | 96...276 V AC 50 Hz |
| Maximum power consumption in VA: | 3 VA at 240 V AC |
| Maximum power consumption in W: | 1 W |
| [Uimp] rated impulse withstand voltage: | 6 kV 1.2/50 µs |
| Mounting mode: | Clip-on |
| Mounting support: | DIN rail |
| Connections - terminals: | Power circuit: tunnel type terminals (bottom) 1 1.65...33 mm² cable(s) solidPower circuit: tunnel type terminals (bottom) 1 1.65...33 mm² cable(s) stranded with cable endCommunication: screw clamp terminals (top) 1 1...4 mm² cable(s) solidCommunication: screw clamp terminals (top) 1 1...2.5 mm² cable(s) stranded with cable end |
| Tightening torque: | Power circuit: 2 N.m PZ2 screwdriver Communication: 0.5 N.m3.5 mm |
| Wire stripping length: | Power circuit: 17 mmCommunication: 7 mm |
| Standards: | IEC 62053-23IEC 62052-31IEC 62052-11IEC 62053-21 |
| Product certifications: | MID conforming to EN 50470-1MID conforming to EN 50470-3CE |
| Compatibility code: | IEM2135 |
| IP degree of protection: | IP40 front panel: conforming to IEC 60529IP20 casing: |
|---|---|
| Overvoltage category: | III |
| Pollution degree: | 2 |
| Flame retardance: | V0 conforming to UL 94 |
| Ambient air temperature for operation: | -25...55 °C |
| Ambient air temperature for storage: | -25...70 °C |
| Operating altitude: | |
| Relative humidity: | 0...95 % at 55 °C |
| Colour: | White |
| 9 mm pitches: | 4 |
| Width: | 36 mm |
| Height: | 90 mm |
| Depth: | 70 mm |
| Net weight: | 0.175 kg |
| REACh Regulation: | Free of Substances of Very High Concern above the thresholdREACh free of SVHC |
| Unit Type of Package 1: | PCENumber of Units in Package 1 |
| Code EAN: | 3606485434643 |
|---|