multifunction voltage control relay RM35-U - range 15..600 V - RM35UA13MW
DESCRIPTION
| Range of product: | Harmony Control Relays |
|---|---|
| Product or component type: | Voltage control relay |
| Relay type: | Multifunction voltage control relay |
| Relay name: | RM35UA |
| Relay monitored parameters: | Overvoltage or undervoltage detection |
| Time delay type: | Adjustable 0.3...30 s, 0 + 10 % on crossing the threshold |
| Switching capacity in VA: | 1250 VA |
| Minimum switching current: | 10 mA at 5 V DC |
| Maximum switching current: | 5 A AC/DC |
| Power consumption in VA: | 0...3.5 VA AC |
| Measurement range: | 15...600 V voltage |
| Utilisation category: | AC-12 conforming to IEC 60947-5-1AC-13 conforming to IEC 60947-5-1AC-14 conforming to IEC 60947-5-1AC-15 conforming to IEC 60947-5-1DC-12 conforming to IEC 60947-5-1DC-13 conforming to IEC 60947-5-1DC-14 conforming to IEC 60947-5-1 |
| Contacts type and composition: | 2 C/O |
| Connections - terminals: | Screw connectors |
| [Uc] control circuit voltage: | 24...240 V |
| [In] rated current: | 5 A |
| Reset time: | 1500 ms time delay |
|---|---|
| Maximum switching voltage: | 250 V AC/DC |
| [Us] rated supply voltage: | 24...240 V AC/DC 50/60 Hz +/- 10 % |
| Supply voltage limits: | 20.4...264 V AC/DC |
| Maximum power consumption in W: | 0.6 W DC |
| Immunity to microbreaks: | 10 ms |
| Control circuit frequency: | 40...70 Hz +/- 10 % |
| Resistance across terminals: | 150 mOhm at E1-M terminals300 mOhm at E2-M terminals600 mOhm at E3-M terminals |
| Output contacts: | 2 C/O |
| Nominal output current: | 5 A |
| Maximum measuring cycle: | 30 ms measurement cycle as true rms value |
| Hysteresis: | 5...50 % of threshold setting |
| Run-up delay at power-up: | 600 ms |
| Measurement accuracy: | +/- 10 % of the full scale value |
| Repeat accuracy: | +/- 0.5 % for input and measurement circuit+/- 2 % for time delay |
| Measurement error: | +/- 0.05 %/°C with temperature variation |
| Polarity: | Non reversible polarity on DC supply |
| Sensitivity scale: | 15...150 V E1-M terminals30...300 V E2-M terminals60...600 V E3-M terminals |
| Threshold setting: | 10...100 % |
| Quality labels: | CE |
| Overvoltage category: | III conforming to IEC 60664-1 |
| Insulation resistance: | > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1 |
| [Ui] rated insulation voltage: | 250 V conforming to IEC 60664-1600 V conforming to IEC 60664-1 |
| Control circuit voltage limits: | - 15 % + 10 % Un |
| Operating position: | Any position without derating |
| Connections - terminals: | Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable endScrew terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable endScrew terminals, 1 x 0.2...2 x 2.5 mm² (AWG 24...AWG 12) flexible with cable endScrew terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end |
| Tightening torque: | 0.6...1 N.m conforming to IEC 60947-1 |
| Housing material: | Self-extinguishing plastic |
| Local signalling: | LED (green) for power ONLED (yellow) for relay ON |
| Mounting support: | 35 mm symmetrical DIN rail conforming to EN/IEC 60715 |
| Electrical durability: | 100000 cycles |
| Mechanical durability: | 30000000 cycles |
| Operating rate: | |
| Safety reliability data: | B10d = 290000MTTFd = 308.2 years |
| Width: | 35 mm |
| Product weight: | 0.08 kg |
| Compatibility code: | RM3 |
| Electromagnetic compatibility: | Emission standard for industrial environments conforming to EN/IEC 61000-6-4Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3Immunity for industrial environments conforming to NF EN/IEC 61000-6-2 |
|---|---|
| Standards: | EN/IEC 60255-6 |
| Product certifications: | GOSTULGLC-TickCSA |
| Directives: | 73/23/EEC - low voltage directive89/336/EEC - electromagnetic compatibility |
| Ambient air temperature for storage: | -40...70 °C |
| Ambient air temperature for operation: | -20...50 °C |
| Relative humidity: | 95 % at 55 °C conforming to IEC 60068-2-30 |
| Vibration resistance: | 0.35 mm (f= 5...57.6 Hz) conforming to IEC 60068-2-61 gn (f= 57.6...150 Hz) conforming to IEC 60255-21-1 |
| Shock resistance: | 5 gn conforming to IEC 60068-2-27 |
| IP degree of protection: | IP20 (terminals) conforming to IEC 60529IP30 (casing) conforming to IEC 60529 |
| Pollution degree: | 3 conforming to IEC 60664-1 |
| Dielectric test voltage: | 2 kV, 1 min AC 50 Hz conforming to IEC 60255-52 kV, 1 min AC 50 Hz conforming to IEC 60664-1 |
| Non-dissipating shock wave: | 4 kV conforming to IEC 60255-54 kV conforming to IEC 60664-14 kV conforming to IEC 61000-4-5 |
| Sustainable offer status: | Green Premium productREACh Regulation |
| Code EAN: | 3389119405317 |
|---|