NG125 Vigi NG125 - bloc différentiel - 63A - 4P -230...415V - 30mA - 19015
DESCRIPTION
| Product or component type: | Add-on residual current devices |
|---|---|
| Device short name: | Vigi NG125 |
| Poles description: | 4P |
| [In] rated current: | 63 A |
| Network type: | AC |
| Earth-leakage sensitivity: | 30 mA |
| Earth-leakage protection time delay: | Instantaneous |
| Earth-leakage protection class: | Class A |
| Device location in system: | Outgoer |
|---|---|
| Network frequency: | 50/60 Hz |
| [Ue] rated operational voltage: | 230...415 V AC 50/60 Hz |
| Residual current tripping technology: | Voltage independent |
| [Ui] rated insulation voltage: | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage: | 8 kV conforming to IEC 60947-2 |
| Mounting support: | 35 mm symmetrical DIN rail |
| Electrical connection to mcb: | By screws |
| 9 mm pitches: | 9 |
| Height: | 118 mm |
| Width: | 189 mm |
| Depth: | 81 mm |
| Product weight: | 0.45 kg |
| Electrical durability: | 10000 cycles conforming to IEC 60947-2 |
| Connections - terminals: | Tunnel type terminals rigid wire(s) 1.5...50 mm² maxTunnel type terminals flexible wire(s) 1...35 mm² max |
| Wire stripping length: | 20 mm |
| Tightening torque: | 3.5 N.m |
| Standards: | IEC 60947-2 |
|---|---|
| IP degree of protection: | IP40 conforming to IEC 60947-2 |
| Pollution degree: | 3 conforming to IEC 60947-2 |
| Electromagnetic compatibility: | 8/20 µs impulse withstand, 3000 A conforming to IEC 60947-2 |
| Tropicalisation: | 2 conforming to IEC 60068-1 |
| Relative humidity: | 95 % ( 55 °C ) |
| Operating altitude: | 2000 m |
| Warranty period: | 18 months |
| Code EAN: | 3303430190158 |
|---|---|
| Contexte: |
|