Schneider Electric Fupact Switch disconnector fuse, Fupact INFD160, 160 A, 3 poles 3F, fuse type DIN 000/00, right side control - LV480437
Schneider Electric Fupact Switch disconnector fuse, Fupact INFD160, 160 A, 3 poles 3F, fuse type DIN 000/00, right side control - LV480437

Switch disconnector fuse, Fupact INFD160, 160 A, 3 poles 3F, fuse type DIN 000/00, right side control - LV480437

SKU : LV480437

Regular price €0,00


/

Contact us for price and lead time for this product. Our team will respond quickly.

Lead time: 2–3 weeks – Ships quickly after order confirmation

Switch disconnector fuse, Fupact INFD160, 160 A, 3 poles 3F, fuse type DIN 000/00, right side control - LV480437

DESCRIPTION

Range of product: INF100...160
Range: FuPact
Product name: Fupact INF
Device short name: INFD160
Product or component type: Switch-disconnector-fuse
Device application: Protection
Poles description: 3P
Protected poles description: 3f
Fuse type: DIN
Fuse size: NH000NH00
Network type: ACDC
Network frequency: 50/60 Hz
Control type: Without handle
Rotary handle mounting location: Lateral
Rotary handle mounting style: Extended
Provision for padlocking: Padlockable
Mounting mode: Vertical - horizontal
Mounting support: DIN rail, with specific accessoriesMounting plate
[Ie] rated operational current: AC-22A: 160 A AC 50/60 Hz 220/240 VAC-22A: 160 A AC 50/60 Hz 380/415 VAC-22A: 160 A AC 50/60 Hz 440/480 VAC-22A: 160 A AC 50/60 Hz 500/525 VAC-22A: 160 A AC 50/60 Hz 660/690 VAC-23A: 160 A AC 50/60 Hz 220/240 VAC-23A: 160 A AC 50/60 Hz 380/415 VAC-23A: 160 A AC 50/60 Hz 440/480 VAC-23A: 160 A AC 50/60 Hz 500/525 VAC-23B: 160 A AC 50/60 Hz 660/690 VDC-22B: 160 A DC 220 V 2 poles in seriesAC-23A: 100 A AC 50/60 Hz 660/690 VDC-23B: 100 A DC 220 V 2 poles in seriesDC-21B: 160 A DC 440 V 4 poles in series
[Ith] conventional free air thermal current: 128 A ( 60 °C ) vertical160 A ( 40 °C ) vertical113 A ( 70 °C ) horizontal121 A ( 65 °C ) horizontal113 A ( 70 °C ) vertical128 A ( 60 °C ) horizontal121 A ( 65 °C ) vertical135 A ( 55 °C ) horizontal142 A ( 50 °C ) horizontal135 A ( 55 °C ) vertical142 A ( 50 °C ) vertical148 A ( 45 °C ) horizontal154 A ( 40 °C ) horizontal148 A ( 45 °C ) vertical160 A ( 35 °C ) horizontal
[Ithe] conventional enclosed thermal current: 135 A at 40 °C, Power dissipation per fuse: 12 W (300 mm x 350 mm x 200 mm)160 A at 40 °C, Power dissipation per fuse: 10 W (300 mm x 350 mm x 200 mm)
Maximum power: 110 kW at 500/525 V AC 50/60 Hz132 kW at 660/690 V AC 50/60 Hz45 kW at 220/240 V AC 50/60 Hz80 kW at 380/400 V AC 50/60 Hz90 kW at 415 V AC 50/60 Hz
Rated duty: Uninterrupted
Intermittent duty class: Class 120 - 60 %
[Ui] rated insulation voltage: 1000 V AC 50/60 Hz1000 V DC
[Uimp] rated impulse withstand voltage: 12 kV
[Ue] rated operational voltage: 690 V AC 50/60 Hz690 V AC 50/60 Hz AC-20690 V DC DC-20500 V DC
[Im] rated making and breaking capacity: Icm 105 kA at 690 V conforming to DIN (with fuse)Icm 176 kA at 415 V conforming to BS (with fuse)Icm 220 kA at 500 V conforming to DIN (with fuse)Icn 100 kA at 500 V conforming to DIN (with fuse)Icn 50 kA at 690 V conforming to DIN (with fuse)Icn 80 kA at 415 V conforming to BS (with fuse)Icm 15 kA at 690 V (without fuse)Icm 22 kA at 415 V (without fuse)Icm 22 kA at 500 V (without fuse)
Suitability for isolation: Yes
Contact position indicator: Yes
Visible break: No
Contact operation: Double-break
Mechanical durability: 10000 cycles
Electrical durability: AC-22A: 1500 cycles 500 V AC 50/60 HzAC-22A: 1500 cycles 690 V AC 50/60 HzAC-23A: 1500 cycles 500 V AC 50/60 HzAC-23A: 1500 cycles 690 V AC 50/60 Hz
[Icw] rated short-time withstand current: 5 kA for 1 s0.95 kA for 30 s1.15 kA for 20 s2.9 kA for 3 s
Design: Horizontal design
Connections terminals: Screw connection
Connections - terminals: Screw connection M8 160 A
Tightening torque: 15...22 N.m for terminal
Height: 140 mm
Width: 181.5 mm
Depth: 142 mm
Standards: EN/IEC 60947-1EN/IEC 60269-4EN/IEC 60269-1EN/IEC 60947-5EN/IEC 60947-3
Product certifications: CCC
IP degree of protection: IP20 conforming to IEC 60529IP65 conforming to IEC 60529
IK degree of protection: IK07 conforming to EN 50102IK10 conforming to EN 50102
Pollution degree: 3
Ambient air temperature for operation: -25...70 °C
Ambient air temperature for storage: -50...85 °C
Compatibility code: INF100...160
Sustainable offer status: Green Premium productREACh Regulation
Code EAN: 3606480343636