TeSys F contactor - 3P(3 NO)-AC-1 <= 1000 V AC 2100 A with coil LX1/ LX9 - 110…500V AC 40/400Hz, LX4 - 110...440V DC - LC1F2100
DESCRIPTION
| Range of product: | TeSys F |
|---|---|
| Range: | TeSys |
| Product name: | TeSys F |
| Product or component type: | Contactor |
| Device short name: | LC1F |
| Contactor application: | Resistive load |
| Utilisation category: | AC-1 |
| Poles description: | 3P |
| Pole contact composition: | 3 NO |
| [Ue] rated operational voltage: | |
| [Ie] rated operational current: | 2100 A (at |
| [Uc] control circuit voltage: | 110...500 V AC 40...400 Hz with LX1/LX9 coil110...440 V DC with LX4 coil |
|---|---|
| [Uimp] rated impulse withstand voltage: | 8 kV |
| Overvoltage category: | III |
| [Ith] conventional free air thermal current: | 2100 A (at 40 °C) |
| Irms rated making capacity: | 3150 A AC conforming to IEC 60947-4-1 |
| Rated breaking capacity: | 3150 A for power circuit conforming to IEC 60947-4-1 |
| [Icw] rated short-time withstand current: | 10000 A 40 °C - 10 s for power circuit7500 A 40 °C - 30 s5500 A 40 °C - 1 min4200 A 40 °C - 3 min3000 A 40 °C - 10 min |
| Associated fuse rating: | 2000 A gG at |
| Average impedance: | 0.1 mOhm - Ith 2100 A 50 Hz |
| [Ui] rated insulation voltage: | 1000 V conforming to IEC 60947-4-11500 V conforming to VDE 0110 group C1000 V conforming to UL 60947-4-1 |
| Control circuit voltage limits: | Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coilDrop-out: 0.3...0.55 Uc AC 40...400 Hz with LX1/LX9 coilOperational: 0.85...1.1 Uc DC with LX4 coilDrop-out: 0.2...0.35 Uc DC with LX4 coil |
| Power dissipation per pole: | 200 W AC-1 |
| Heat dissipation: | 18 W |
| Operating time: | 40...75 ms closing for with LX1/LX9 coil100...170 ms opening for with LX1/LX9 coil50...60 ms closing for with LX4 coil45...60 ms opening for with LX4 coil |
| Mounting support: | Plate |
| Standards: | JIS C8201-4-1EN 60947-1EN 60947-4-1IEC 60947-4-1IEC 60947-1UL 60947-4-1CSA C22.2 No 60947-4-1 |
| Product certifications: | CCCULCB SchemeCSAEACUKCA |
| Connections - terminals: | Power circuit: bar 4 cable(s) Power circuit: bolted connectionControl circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable endControl circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible with cable endControl circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable endControl circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²solid without cable endControl circuit: screw clamp terminals 1 cable(s) 1...4 mm²Control circuit: screw clamp terminals 2 cable(s) 1...4 mm² |
| Tightening torque: | Power circuit: 58 N.mControl circuit: 1.2 N.m |
| Mechanical durability: | 0.5 Mcycles |
| Inrush power in VA: | 1600...2400 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil2000...2200 VA (at 20 °C)with LX4 coil |
| Hold-in power consumption in VA: | 29...37 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil8...10 VA (at 20 °C)with LX4 coil |
| Maximum operating rate: | 600 cyc/h 55 °C |
| Protective treatment: | TH |
|---|---|
| Ambient air temperature for operation: | -5...40 °C |
| Ambient air temperature for storage: | -60...80 °C |
| Permissible ambient air temperature around the device: | -40...60 °C |
| Operating altitude: | 3000 m without derating |
| Mechanical robustness: | Vibrations contactor open: 2 Gn, 5...300 HzVibrations contactor closed: 4 Gn, 5...300 HzShocks contactor open: 6 Gn for 1/2 sine wave (11 ms)Shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms) |
| Height: | 332 mm |
| Width: | 438 mm |
| Depth: | 238.6 mm |
| Product weight: | 31 kg |
| REACh Regulation: | Free of Substances of Very High Concern above the thresholdEU RoHS Directive |
| Code EAN: | 3389118372658 |
|---|