Schneider Electric TeSys TeSys K -Time delay auxiliary contact block - 1 C/O - 24...48 V - 1…30s - LA2KT2E
Schneider Electric TeSys TeSys K -Time delay auxiliary contact block - 1 C/O - 24...48 V - 1…30s - LA2KT2E

TeSys K -Time delay auxiliary contact block - 1 C/O - 24...48 V - 1…30s - LA2KT2E

SKU : LA2KT2E

Regular price €0,00


/

Contact us for price and lead time for this product. Our team will respond quickly.

Lead time: 2–3 weeks – Ships quickly after order confirmation

TeSys K -Time delay auxiliary contact block - 1 C/O - 24...48 V - 1…30s - LA2KT2E

DESCRIPTION

Range: TeSys
Range of product: TeSys K control relayTeSys K
Product name: TeSys K
Product or component type: Time delay auxiliary contact block
Device short name: LA1
Range compatibility: TeSys K LC1KTeSys K CA2KTeSys K CA3KTeSys K CA4K
Mounting location: Front
Pole contact composition: 1 C/O
Auxiliary contacts operation: Time delay
Timer type: On delay
Time delay range: 1...30 s
[Ue] rated operational voltage: 24...48 V AC/DC for control circuit240 V AC for signalling circuit
Rated operational voltage limits: 0.85...1.1 Uc
[Ith] conventional free air thermal current: 2 A for signalling circuit
Standards: EN/IEC 60947-5-1UL 60947-5-1CSA C22.2 No 60947-5-1
Reset time: 1.5 s during time delay0.5 s after time delay
Insulation resistance: > 10 MOhm
Connections - terminals: Slip-on terminals
Shielding continuity terminal: Without
Height: 27 mm
Width: 38 mm
Depth: 38 mm
Product weight: 0.04 kg
Compatibility code: LA1
Environmental characteristic: Normal environment
IP degree of protection: IP20 conforming to IEC 60529
Protective treatment: TC conforming to IEC 60068
Ambient air temperature for operation: -10...60 °C
REACh Regulation: Free of Substances of Very High Concern above the thresholdEU RoHS Directive
Code EAN: 3389110230048